VF(R)-12 Embedded High Voltage AC Vacuum Load Switch

VFR-12R AC Vacuum Load Switch is a new generation of high voltage vacuum switching equipment, developed specifically to meet market demand and modern design concepts. It is mainly used in indoor armored air-insulated switchgear and is capable of stable operation within the specified voltage range under normal conditions.
Product Details

Overview of VF(R)-12

VF(R)-12 is a kind of indoor embedded high voltage AC vacuum load switch-fuse combination device. It is suitable for various power grids and operates safely and stably within its technical parameters. With advanced design, this device is widely used in modern power systems.

Product standard

VF(R)-12 Vacuum load switch conforms to the following standards:

GB 3804-2004: High-voltage load AC switches with rated voltage between 3.6 kV and 40.5 kV.
GB 16926-2009: Standard for high-voltage load AC switch-fuse combinations.

Technical Parameters

ItemUnitReference value
VF-12/T630-20
Vacuum load
switch
VFR-12/T125-50
Vacuum load
switch-fuse
combination
VFH-12/T630-25
High breaking
capacity vacuum
switch
VFHR-12/T125-50
High breaking
capacity vacuum
switch-tuse
combination
Rated yoltagekV12121212
ightning impulse withstand voltagekV75757575
Rated insulation level 1min power-frequency withstand voltagekV42424242
Rated frecuencyHz50/6050/6050/6050/60
Rated currentA630125(fuse)630125(fuse)
Rated short-circuit breaking currentkA 50(fuse25(are suppreson chamber)25im pcesson harx
Rated short-circuic making current (peak value)kA50 63 
Rated short-time withstand currentkA20 25 
 Rated withstand current (peak value)kA50 63 
 Rated breaking current of cable during chargeA16   
Rated breaking current of no-load transformerkVA1250 1250 
Rated breaking take-over currentA 3150 3150
Breaking times of the rated short-circuit currentTimes    
Mechanical life M2 levelM2 leveM2 leveM2 level
Weightkg125

Operating conditions

Ambient temperature: -40°C to +40°C (less than 35°C within 24 hours)
Relative humidity: ≤95% (daily average), or ≤90% (monthly average)
Altitude: ≤1000 meters

Transformer and fuse selection

Fuses have the ability to cut off high currents in less than 10 milliseconds and have a breaking capacity of up to 50KA, which makes them effective in protecting transformers. When selecting fuses, it is important to consider that the fuse current needs to be 1.6 times its rated value to cope with potential inrush currents. The designer should also allow a margin for the fuse, taking into account the fluctuations in the grid. If the fuse is to be used for high voltage motor protection, consideration should also be given to the frequency of motor start-ups, as frequent start-ups may result in the fuse not being able to cool down in time and thus failing.

Fuse Selection

Primary voltage of
the transformer(kV)
Capacity of
the transformer(kVA)
Model of the fuseRated current
of the fuse(A
Model for the domestic marketModel for international market
6.6200XRNT-1012kV BDGHC31.5
25040
300/31550
40012kV BDGHC63
50080
63090

Overall And Installation Dimension

Overall dimension of VF(R)-12(wheeled)indoor high-voltage alternating-current vacuum circuit breaker

AC-Vacuum-Load-Switch
Cabinet width(mm)P(mm)A(mm)B(mm)C(mm)E(mm)φW(mm)
65015050053049020335
80021065068064027835
100027585088084037835